¢Ú wind pipe and valves, air speed is too large , resulting in airflow noise , adjust valves, vents , reducing the wind speed is too high .
¢Û equipment silencer duct system is imperfect , increase silencer elbow and other equipment.
5 , total air volume system does not match the total amount of wind , the larger the difference between the causes and solutions ¢Ù wind measurement methods and calculations are incorrect , please review the measurement and calculation data .
¢Ú system airflow leakage or short circuit , check plugging eliminate short circuit.
6 , indoor air velocity distribution does not have a dead causes and solutions ¢Ù airflow design ill-considered, should be measured according to the airflow distribution , adjust the position or increase the number of outlet outlet .
¢Ú outlet air volume is not adjusted evenly, does not meet the design value should be adjusted so that each outlet air flow in line with the design requirements