Service Manual Transistor Technical Articles CD Download Register Member Login Exit Sign
Home A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
. TV  .  Camera  .  Video camera  .  Notebook  .  Audio  .  Monitor  .  Projector  .  Air conditioning  .  Refrigerator  .  Printer  .  Duplicator  .  Fax machine  .  Mobile  .  Telephone  .  Washing machine  .  Cooker  .  Microwave  .  Other  .  
Your current location£ºHome > Technical Articles > Air conditioning

Panasonic CU-140C52XN ceiling type air conditioning cannot start the repair method of fault

Time£º2014-07-05 08:05:57  Source£ºNetwork  Author£ºUnknown  Clicks£º11042
  
RyTservice manual download site
 RyTservice manual download site
Special emphasis on here, when R1 open circuit, high voltage on both ends of the CN1, big circuit board for compressor running current, and so cannot be started. Measuring resistance of 550 Ω on both ends of the R1, can judge the R1 open (because the CT1 coil resistance is 550 Ω, only for R1 on both ends of the resistance measured 420 Ω is normal). Repair many sets of this type of air conditioning, all found the little board diode or damage resistance. RyTservice manual download site
 RyTservice manual download site
Any damage of a resistance small circuit boards, all can cause air conditioning fault cannot be started. Repair, therefore, this model cannot be started when the air conditioning, might as well start from small circuit board, can get twice the result with half the effort, of course, for other models also have launched air conditioning can draw lessons from action.RyTservice manual download site